If you have been in search of Alarm Gas Automatic products that are listed with the NSN 6665015302725 we have you covered here on Speedy NSN. You have reached the RFQ page for part number CM-21A a Aerion Technologies Inc item that is readily available for procurement from our website at any time. Whether you wish to purchase this part or simply want to receive more information for your comparisons, be sure to fill out and complete the form provided on this page with as much detail as you can regarding your needs and restrictions. Within 15 minutes of us receiving and reviewing a completed form, a member of our staff will reach out to you to present a customized quote that keeps your part requirements in mind.
Note : We Will Not Share Your Information To Any Third Parties.
To ensure that customers only procure the exact items they are looking for, we list products with as much information as possible. For example, this particular Aerion Technologies Inc part was produced under the CAGE Code 2Y359, ], a unique identifier assigned to manufacturers who have been approved to supply government entities. Additionally, with the NSN 6665-01-530-2725 this product also belongs to the FSC 6665 Hazard Detecting Instruments And Apparatus. If you ever have any questions regarding our offerings or services, be sure to call or email us at your convenience. Get started on the purchasing process today so we can fulfill all your operational needs as your strategic sourcing partner.
MRC | Criteria | Characteristic |
---|---|---|
APGF | DESIGN TYPE | NONTRIPOD MOUNTING |
AFJK | III CUBIC MEASURE | 38.250 CUBIC INCHES |
SUPP | III SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
FEAT | SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
BRQN | MEDIA DETECTED | CARBON MONOXIDE |
CXCY | III PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |
ALBY | USAGE DESIGN | INDUSTRIAL |
ALXZ | SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
AMKD | INDICATOR TYPE | RED LIGHT AND HORN |